Fault Trapper

The only way to see why, when and where a circuit breaker trips

Stop guessing about circuit breaker tripping issues!
You can now detect the type of fault, and locate the position of an electrical “event” that causes intermittent/persistent circuit breaker trips, and No Fault Found (NFF) conditions. The critical information needed to reduce call backs for circuit breaker trips.

The Fault Trapper™ is a new class of tester that uses Spread Spectrum Time Domain Reflectometry (SSTDR) to monitor live circuits. The Fault Trapper™ can capture time and distance to Opens, Shorts and Arc Faults saving the event information in memory for later investigation. If the circuit breaker trips, the backup battery powers the Fault Trapper™ to allow for an orderly shutdown. The last faults can be viewed using the battery power. The In-Line Adapter isolates the circuit being monitored from the breaker panel and all other breakers.

PRODUCT FEATURES

  • No Splicing Required – Plug in existing wiring
  • In-Line monitoring of energized branch circuits up to 300 VAC and 40 amps
  • SSTDR (Spread Spectrum Time-Domain Reflectometry) for accurate Fault Locating
  • Fault Location reported as distance from Fault Trapper™ in feet/meters
  • Easy-to-Use Three button Operation
  • Backlit LCD Display with Simple User Interface
  • Back-up battery allows capture of breaker trips/Unpowered display of results

PHYSICAL FEATURES

Fault Trapper Main Unit
Size: 15.25 x 7.6 x 3.8 cm (6.0 x 3.0 x 1.5 inches)
Weight: 255 grams (9 oz.) With battery

40amp In-Line Adapter
Size: 11.5 x 7.6 x 5.85 cm (4.5 x 3.0 x 2.3 inches)
Weight: 312 grams (11 oz.)

Physical DimensionsFault Trapper Main Unit
Size: 15.25 x 7.6 x 3.8 cm (6.0 x 3.0 x 1.5 inches)
Weight: 255 grams (9 oz.) With battery
40amp In-Line Adapter
Size: 11.5 x 7.6 x 5.85 cm (4.5 x 3.0 x 2.3 inches)
Weight: 312 grams (11 oz.)
Input RatingFault Trapper Main Unit: 90 to 265 Volts ac rms 50/60 Hz, 4 watts max.
40amp In-Line Adapter: 300 Volts ac rms, 40 amp circuits maximum, supplies power to main unit
Measurement Method. Spread Spectrum Time Domain Reflectometry (SSTDR)
Accuracy: +/-10%
Maximum Length: 300 ft on NM-B or Wire in Conduit
Battery Use and LifeUsed to review results when not AC powered
Battery Low Level: Approximately 5.5 volts
Battery Life (9 Volt alkaline battery, typical) - Standby: 2 years
Active: 4 hours typical
Environmental TemperatureTemperature - Operating: 0 to 50°C (32 to 122°F)
Storage temperature: -20 to 60°C (-4 to 140°F)
Long Term Storage w/ battery: 35°C maximum (95°F)
Humidity: 10% to 90%, non-condensing
Altitude: 2,000 meters (6,561ft) maximum
Rating300V CAT III, 120/240Vac, 40 amps or less, single phase
Safety ComplianceTUV, CE
Fault Trapper Datasheet (English)Download
Fault Trapper User Manual (English)Download

“[LiveWire Innovation] delivered and demonstrated a unit which we immediately used to accurately locate a cable fault on one of our sub-sea 5 KV cables. Prior to this we had used conventional TDR meters which had given us unreliable results and showed ghost signals which could have indicated additional faults that didn’t exist. The cost implications of this are huge.”

-Mike Mason, Dubai Petroleum

“[LiveWire Innovation] delivered and demonstrated a unit which we immediately used to accurately locate a cable fault on one of our sub-sea 5 KV cables. Prior to this we had used conventional TDR meters which had given us unreliable results and showed ghost signals which could have indicated additional faults that didn’t exist. The cost implications of this are huge.”

-Mike Mason, Dubai Petroleum

Fault Trapper Kit

FT100-M

  • Fault Trapper main unit
  • 40 amp in-line adapter
  • Two plug-in 2-wire terminal block connectors – 8-to -24 AWG (0.2 to 10 mm)
  • Banana plug leader cable

Handheld Solutions

Fully housed sensor modules for permanent installation. Handheld products using LiveWire’s Spread Spectrum brand of TDR for maintenance, field testing and electrical contractor markets.

The Mantis™ LW-MM200 is the first live cable tester module that monitors energized cable run faults and electrical circuits around-the-clock.

Fault Trapper monitors live circuits for intermittent conditions to record time and distance to Opens, Shorts and Arc Faults.

Dual mode TDR for testing and monitoring energized and unenergized systems.

Power Prowler

3-In-1 DMM/TDR Cable Fault Finder

FaultChaser Handheld

Fault Finding/Cable Length Measurement TDR